Fully Sealed SF₆ Gas-Insulated Ring Main Unit
HXGNP-12
A pioneer product in the domestic market with IP67 protection for the entire unit. It is engineered for harsh, damp environments and locations with a high risk of flooding, such as basements.
Product Description
As a domestic pioneering product, the entire unit (including the secondary instrument compartment) achieves an IP67 protection rating, completely eliminating issues such as condensation and mechanism corrosion. It can operate in temporary submersion environments, making it suitable for harsh, humid, and flood-prone locations like basements. It supports both manual and motorized operations, comes equipped with automated protection functions, provides reliable interlocking, and fully complies with domestic safety operating regulations.
3D 模型加载中...
3D 模型加载失败,请检查 GLB 文件格式、压缩扩展或服务器响应。
Product Advantages
High Protection Capability
Capable of short-term submerged operation with an IP67 protection rating.

Reliable & Maintenance-Free
Completely eliminates mechanism corrosion caused by damp heat and condensation, featured with a fully functional 'five-proofing' mechanical interlock.

All-Around Operational Requirements
Supports manual/motorized and remote/local operation functions.

Complete Product Range
C/V/D/PT units, common-tank type, extensible units, standardized dimensions.

Full Design Schemes
The installation dimensions fully comply with the standard schemes of the State Grid and China Southern Power Grid.

High Adaptability
The product supports both common-tank and top-extension configurations.

Primary and Secondary Integration
Seamlessly compatible with standardized distributed DTUs.

Fully Sealed SF₆ Gas-Insulated Ring Main Unit
HXGNP-12
Technical Specifications
| Rated Voltage | 12kV |
| Arc Extinguishing Chamber Type | Vacuum |
| Rated Frequency | 50Hz |
| Rated Current | 630A |
| Rated Short-Time Withstand Current & Duration | 20kA/4s |
| Rated Peak Withstand Current | 50kA |
| Arcing Duration | ≥0.5s |
| Protection Rating | Gas Tank: IP67 |
| Secondary Compartment: IP67 | |
| Rated Gas Pressure (20°C Gauge) | 0.04MPa |
| Annual Gas Leakage Rate | 0.05% V/V |