Integrated DC Energy Meter
DC meters designed for application scenarios such as DC power panels, EV charging piles, and telecom base stations.
Product Description
Utilizing microelectronics technology to measure DC energy, featuring multi-protocol support, ultra-low power consumption, and matching use with EV charging piles, it is equipped with functions such as LCD display, energy metering, clock, RS485 communication, electrical and second pulse output, and instantaneous data measurement and monitoring, suitable for DC energy metering.
The technical indicators comply with the requirements of the GB/T 33708-2017 standard, “Static Meters for Direct Current Energy,” equipped with 2x independent RS485 interfaces that support the DL/T 645-2007 protocol as well as Modbus-RTU, a widely used industrial protocol, for easy and rapid integration.

Product Advantages








Integrated DC Energy Meter
DJZ208
| Technical Parameters | |
| Basic Electrical Parameters | |
| Reference Voltage (Un) | 1000V |
| Reference Current (In) | 100A |
| Maximum Voltage | 1.15Un |
| Maximum Current | 300A, 400A |
| Minimum Current (Imin) | 1%In |
| Starting Current (Ist) | 2‰In |
| Creeping | Anti-creeping |
| Operating Voltage Range | DC9V-30V |
| Accuracy Class | |
| Accuracy Class | 0.5 |
| Pulse Constant | |
| Optical Pulse Constant | 1000 imp/kWh, configurable 50-1000 imp/kWh |
| Electrical Pulse Constant | 1000 imp/kWh, configurable 50-1000 imp/kWh |
| Power Consumption | |
| Voltage Circuit Power Consumption | ≤0.5W |
| Current Circuit Power Consumption | ≤40mW/A*lmax |
| Auxiliary Power Consumption | ≤2W |
| Clock Accuracy | |
| Clock Accuracy | ±0.1s/℃/24h (at 23℃) |
| Data Storage | |
| Data Retention after Power Failure | >10 years |
| Environmental Parameters | |
| Operating Temperature Range | -25℃~+60℃ |
| Limit Temperature Range | -40℃~+70°C |
| Storage and Transport Temperature Range | -40℃~+70℃ |
| Storage and Operating Humidity | Annual average ≤75% |