Distributed Distribution Terminal Unit
Product Description
The Distributed Distribution Terminal Unit (DTU) is a core piece of equipment in distribution automation. Utilizing a decentralized architecture, it consists of bay units (installed within switchgear cubicles) and a common unit (for centralized management) that collaborate seamlessly via a communication bus. It is primarily deployed in ring main units (RMUs), switching stations, and distribution rooms within 10kV networks.
The HXD320-DCU distribution automation common unit is responsible for acquiring data from measurement and control units. It communicates with the master station system to upload and report all collected information.
The HXD320-CMU distribution automation bay unit performs measurement, protection, and control for the switchgear to enable distribution automation functions. It communicates with the HXD320-DCU management unit to upload and report all collected information.
Product Advantages
Distributed Distribution Terminal Unit
Technical Specifications
| Parameter Name | Parameter | Remarks |
| Device Power Supply | DC48V | |
| Communication Power Supply | DC24V | |
| Digital Inputs | 7 digital inputs per bay. | |
| Analog Inputs | Measures ABC three-phase voltage of one bus section and one zero-sequence voltage; measures ABC three-phase current and zero-sequence current per bay. | |
| Output Circuits | Two remote control outputs (open/close) and two protection outputs (open/close) per bay. | |
| Communication Interfaces | 1 Bluetooth interface; 1 hot-swappable 4G/5G module interface; 3 RS485 communication interfaces; 1 serial debug interface; 1 hot-swappable wireless communication module interface; 2 100M Ethernet interfaces. | |
| Installation Method | Shielded vertical, cabinet dimensions: no larger than 1300*600*400mm (excluding communication box). | |
| Metering Function | Built-in line loss metering. | |
| Protection Functions | Three-stage overcurrent protection, two-stage zero-sequence current protection, short-circuit fault alarm, small current grounding line selection, three-shot auto-reclosing, non-interrupting current blocking, under-voltage alarm, zero-sequence overvoltage alarm, PT disconnection alarm, post-acceleration protection. | |
| Time Synchronization | GPS/Beidou time synchronization. | |
| DTU Connection Type | Rectangular aviation connector | 26 pins |
| Backup Power Supply | Rated voltage DC48V, single battery cell no less than 12Ah, service life ≥3 years, capable of completing "open-close-open" operation and maintaining operation of the distribution terminal and communication module for at least 4 hours. | Optional 20Ah, 24Ah, or other capacities based on user requirements. |