Containerized Substation
Containerized Substation: A complete power distribution assembly that integrates high-and-low voltage equipment, transformers, and other components into a mobile steel enclosure.
Product Description
Containerized substation, fully known as container-type prefabricated substation, is a complete power distribution assembly that organically integrates high-voltage switchgear, distribution transformers, low-voltage switchgear, energy metering equipment, and reactive power compensation devices into a sealed, movable steel-structure enclosure. It is suitable for three-phase AC systems with a rated voltage of 6-10/0.4kV, 24/0.4kV, and 40.5/0.4kV, serving for line power distribution and allocation.

Product Advantages
All-in-One Integrated Design
Transformers, high-and-low voltage distribution equipment, and smart monitoring systems are fully integrated into a standard container. This enables true "plug-and-play" functionality, significantly shortening the on-site installation period.

Modular Structure
Internal equipment utilizes a modular design, supporting customized configurations to adapt to diverse capacities and functional requirements (such as solar PV, energy storage grid connection, and wind power).

Eco-Friendly & Energy-Saving
Utilizing an eco-friendly anti-corrosion treatment process, the production phase ensures low pollution and low energy consumption.

Smart O&M
It can be configured with an intelligent substation measurement and control device to measure and protect the electrical equipment within the enclosure, enabling real-time monitoring of product operational data.

Containerized Substation
YB-12/24/40.5kV
YB-12kV
| Item | Parameter |
| Rated Voltage kV | 12 |
| Rated Frequency Hz | 50/60 |
| Rated Capacity kVA | 100~2500 |
| Rated Power Frequency Withstand Voltage kV | HV Cabinet 42 |
| Isolation Gap 48 | |
| Transformer 35 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet 75 |
| Isolation Gap 85 | |
| Transformer 75 | |
| HV Side Configuration | 12kV Ring Main Unit |
| Transformer Type | Oil-immersed (Dry-type optional) |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) |
| Equipment Dimensions (LWH) | 6058*2438*2591 mm |
| Enclosure Specification | 20ft Standard High Cube Container |
YB-24kV
| Item | Parameter |
| Rated Voltage kV | 24 |
| Rated Frequency Hz | 50/60 |
| Rated Capacity kVA | 100~2500 |
| Rated Power Frequency Withstand Voltage kV | Phase-to-Ground and Phase-to-Phase 65 |
| Isolation Gap 79 | |
| Transformer 55 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet 125 |
| Isolation Gap 145 | |
| Transformer 125 | |
| HV Side Configuration | 24kV Ring Main Unit |
| Transformer Type | Oil-immersed (Dry-type optional) |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) |
| Equipment Dimensions (LWH) | 6058*2438*2591 mm |
| Enclosure Specification | 20ft Standard High Cube Container |
YB-40.5kV
| Item | Parameter | |
| Rated Voltage kV | 40.5 | |
| Rated Frequency Hz | 50/60 | |
| Rated Capacity kVA | 1000~6300 | |
| Rated Power Frequency Withstand Voltage kV | HV Cabinet | 95 |
| Isolation Gap | 118 | |
| Transformer | 85 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet | 185 |
| Isolation Gap | 215 | |
| Transformer | 200 | |
| HV Side Configuration | 40.5kV Ring Main Unit | |
| Transformer Type | Oil-immersed (Dry-type optional) | |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) | |
| Equipment Dimensions (LWH) | 6058*2438*2896 mm | |
| Enclosure Specification | 20ft Standard High Cube Container |